BTU calculator for radiators: what size do I need?
Heat loss in watts and BTU/h, surface by surface, and the radiator size at your flow temperature. Free, no sign-up.
The room
Step 1 of 8Where and when
Step 2 of 8Outside walls
Step 3 of 8Windows and doors
Step 4 of 8No windows or doors in the outside wall
Ceiling and floor
Step 5 of 8Ground floor
Step 6 of 8Not needed: nothing below this room is ground
Air
Step 7 of 8Your radiator
Step 8 of 8Radiator size for this room
Example room: a 1930s semi's living room in Manchester. Change anything to make it yours.
Look for a radiator rated at least
Where the heat goes
Each line is rounded on its own, so they can add up to a watt more or less than the total.
Sizing a boiler or heat pump? That needs the whole home's heat loss plus hot water, worked out by a heating engineer.
An estimate from standard tables, not a heat-loss survey. Before fitting a heat pump, an MCS installer works out every room.
Couldn't copy. Select the text below and copy it yourself.
Calculations stay in your browser. Copy, email and print export your breakdown only when you choose.
How the BTU calculator works
You've got a room that never quite warms up, or a new one with bare plaster and no radiator yet. The question is the same: how much heat does it lose on a properly cold day, and what radiator puts that heat back?
We answer it the way a heating designer does, one surface at a time. Each wall, window, ceiling and floor loses heat in proportion to its area, its U-value and the gap between the room's temperature and the temperature on the other side. A U-value is the watts that pass through one square metre for each degree of difference, so lower is better. A filled cavity wall from the 1930s, at 0.7, lets through less than half of what an unfilled one does at 1.5.
The U-values come from RdSAP 10, the method used for EPCs on existing homes. England, Scotland, Wales and Northern Ireland each have their own tables. The cold day comes from 14 weather stations: Manchester's is -4.5 °C, Plymouth's -1.5 °C, and only about 35 hours of a typical year are colder. A solid ground floor is the exception. It sits on earth that stays at much the same temperature all year, so it uses the region's yearly average instead.
Then we add the air that leaks out, starting at 0.5 air changes an hour for a room with outside surfaces. A fully enclosed room uses zero instead. We also count the devices you select and a small allowance for the joints where walls meet floors and ceilings, which the trade calls thermal bridging.
Take the example the calculator opens with, a 1930s semi in Manchester. The living room is 4.2 by 3.6 m: one outside wall, cavity filled, a double-glazed window, a solid floor and a heated room above. It loses about 570 W on a design-cold day. The wall is a quarter of that, and so is the air. The window is a fifth of the wall's size and loses nearly four-fifths as much as the brickwork around it.
The last step is the radiator. UK catalogues rate radiators at ΔT50: water averaging 70 °C in a 20 °C room. Yours probably isn't running at exactly that, so we turn the room's loss into the rating to look for at your temperatures. Two rooms with the same loss can need different radiators. A bathroom at 22 °C gets less from the same radiator than a bedroom at 18 °C, because the gap between water and room is smaller.
Delta T 50, and why a heat pump needs a bigger radiator
Stelrad's specification book calls ΔT50 "the UK's industry standard for heating outputs". A boiler running at 75 °C out and 65 °C back gets close to the label. A heat pump doesn't. At 45 °C flow and 40 °C return the water averages 42.5 °C, which in a 21 °C living room is a difference of 21.5 degrees. A radiator's output falls faster than that difference does. It gives about a third of its rating.
So the Manchester living room, which needs a 583 W radiator on a boiler at 75/65, needs about 1,700 W of rating on a heat pump at 45/40. A 1,000 W radiator on that wall would give about 330 W there, roughly 230 W short of the 568 W the room loses. A radiator doesn't read its own label.
That's why a heat-pump quote asks about your radiators. Type the catalogue figure of a radiator you're looking at, set your installer's flow and return temperatures, and you'll see what it gives in your room and whether it covers the loss. The correction is the formula behind Stelrad's own table: output times (ΔT divided by 50) to the power 1.3.
Who this is for
Homeowners choosing a radiator for one room: a replacement for one that never kept up, a first radiator in an extension, or a check before a heat pump goes in. It also suits anyone holding a catalogue in BTU and a quote in kilowatts who wants both in the same units. It doesn't size a boiler or a heat pump, which needs the whole house and the hot water too.
Homeowner questions about radiator sizes and BTU
How many BTU do I need for a room?
It depends on what the room loses, and size is only part of that. A 4.2 by 3.6 m living room in a 1930s Manchester semi needs a radiator of about 1,990 BTU/h (583 W) at ΔT50, with one outside wall and a filled cavity. Give the same room an open chimney and it needs more than twice that, about 4,350 BTU/h. A rule of thumb that multiplies floor area by a fixed figure can't see either difference.
What does delta T 50 mean?
It's the condition radiators are rated at in the UK: water going in at 75 °C and coming out at 65 °C, so averaging 70 °C, in a room at 20 °C. The 50 is the gap between the water's average and the room. Run the water cooler, or heat the room warmer, and the radiator gives less than its catalogue figure.
Do I need bigger radiators for a heat pump?
Often, yes. At 45/40 °C a radiator gives about a third of its ΔT50 rating in a 21 °C room, so the rating you need is about three times the room's heat loss. At 55/45 °C it gives about half. Put your installer's flow and return temperatures into the last step to see the figure for your room.
How do I convert radiator watts to BTU?
Multiply watts by 3.412 to get BTU per hour, or divide BTU/h by 3.412 to get watts. A 1,000 W radiator is about 3,412 BTU/h. We use the exact figure behind it (one BTU is 1,055.06 joules) and always convert from the unrounded watts, so the two columns never drift apart.
What temperature should a bedroom be?
For sizing a radiator in an older home, the MCS heat pump standard designs bedrooms at 18 °C, living rooms at 21 °C and bathrooms at 22 °C. Newer homes use 21 °C in most rooms. They're design figures for the coldest days, and you can set your own in the first step if you like it warmer.
How do I calculate the heat loss of a room?
Add up each surface: its area times its U-value times the temperature difference across it. Then add the air: 0.33 watts for each cubic metre swapped per hour, for each degree. A solid ground floor uses the year's average outside temperature rather than the cold-day one, because the ground under it barely changes.
What size radiator for a bathroom?
Bathrooms are designed warmer, at 22 °C, so the same radiator gives them less. A 2.8 by 2.2 m bathroom over a garage in Belfast, with a flat roof above, loses about 450 W. On 55/45 °C water it needs a radiator rated about 960 W at ΔT50. A towel rail rated 1,500 BTU/h gives about 210 W there.
Does an open fireplace make a room colder?
It makes the room harder to heat. SAP 10.2, the government's energy method, counts an open chimney as 80 cubic metres of air an hour. In the Manchester living room that's 673 W on a design-cold day, more than the wall, the window and the floor put together. A properly blocked chimney counts as 20.
What size boiler do I need?
That's a different sum. A boiler or a heat pump is sized from the whole home's heat loss plus its hot water, and before a heat pump goes in, an MCS installer works it out room by room. Here you're sizing one room's radiator. The boiler is a heating engineer's job.
What size radiator do I need?
It's the total on the wall that heats the room. If a room needs 1,700 W at ΔT50, two radiators of 850 W do the same job as one of 1,700 W, and you can type up to three and see them added. Round up to the next size in the range you like: we don't pick a model.
We don't add a safety margin either. The cold day the room is sized for is already colder than all but about 35 hours of a typical year. Your installer may add one. Ask what it's for.
Your EPC helps with the inputs: its Walls, Roof and Windows lines usually name the construction, such as "Cavity wall, filled cavity" or "Pitched, 270 mm loft insulation". Buying in BTU? The figure sits right beside the watts.
Sources and last checked
Dataset btu-radiator-2026-10-07, last checked 8 October 2026.
- U-values, age bands, wall thicknesses, the ground-floor method and thermal bridging: BRE, RdSAP 10 Specification V4.0, 7 June 2026.
- Cold-day temperatures for 14 sites and yearly means for 18 regions: the MCS Heat Load Calculator documentation (CIBSE Guide A 2015, Table 2.5; MCS MGD 007, Table B1). Glasgow is -5.6 °C there; MCS's MIS 3005-D gives -5.9 °C for Glasgow at a different station. We use the first; type the second if your installer works to it.
- Room temperatures: MCS MIS 3005-D Issue 3.0, Table 1, and for newer homes the CIBSE Domestic Heating Design Guide 2026 as MCS publishes it.
- Air: SAP 10.2, Table 2.1 and its 0.33 factor.
- Radiator ratings and the exponent 1.3: Stelrad Specification Radiator Book, October 2024. Our correction is the formula; it matches that book's table, and Stelrad's web table differs from it by up to 0.002.
- Watts to BTU/h: NIST SP 811 (1 BTU/h = 0.2930711 W).